#' @title calc_trafo_impedance
#' @description function that calculates the impedance of transformers
#' @param solution_space dataframe containing possible transformer types in the grid and its specifications
#' @param Vref reference voltage in the grid, default value is 400 V for low voltage distribution grid
#'
#' @return solution_space data with impedance
################################################################################
calc_trafo_impedance <- function(solution_space, Vref = 400){
S_n <- solution_space$S
u_k <- solution_space$uk
P_cu <- solution_space$PCu
U_1n <- solution_space$trafo_U1
#calculating normal current for further calculation
I_1n <- S_n*1000/(sqrt(3)*U_1n)
# if that is all ok from a normalizing point of view?
I_ref <- I_1n * U_1n/Vref
############# calculating transformer Parameters
########### seriel element
Z_k <- u_k*(Vref*sqrt(3))^2/(S_n * 1000)
R_k <- P_cu*1000/1/(I_ref^2)
X_k <- sqrt(Z_k^2 - R_k^2)
# writing results
solution_space$R <- R_k
solution_space$X <- X_k
return(solution_space)
}