#' Minenergo-325. Normative heat loss data
#'
#' Data represent values of specific heat loss power officially accepted by
#' \href{https://docs.cntd.ru/document/902148459}{Minenergo Order 325} as
#' norms. Those values are maximums which are legally
#' affirmed to contribute to normative heat loss \eqn{Q_{NHL}} of
#' district heating systems with water as a heat carrier.
#'
#' Data is organized as a full factorial design, whereas for some factorial
#' combinations \href{https://docs.cntd.ru/document/902148459}{Minenergo Order 325}
#' does not provide values. For that cases values are postulated by practical
#' reasons in Siberian cities and marked with source label \emph{sgc}.
#'
#' Usually the data is not used directly. Instead use function \code{\link{m325nhl}}.
#'
#' @family Minenergo
#'
#' @format A data frame with 17328 rows and 8 variables:
#' \describe{
#' \item{source}{Identifier of data source: identifiers suited with
#' glob \emph{t?p?} mean appropriate \emph{table ?.?} in
#' \href{https://docs.cntd.ru/document/902148459}{Minenergo Order 325};
#' identifier \emph{sgc} means that values are additionally
#' postulated (see \emph{Details}).
#' Type: \code{\link{assert_character}}.
#' }
#' \item{epoch}{Year depicting the epoch when the pipe is put in operation after laying or total overhaul.
#' Type: \code{\link{assert_integer}}.}
#' \item{laying}{Type of pipe laying depicting the position of pipe in space. Only five types of
#' pipe laying are considered:
#' \itemize{
#' \item \code{air},
#' \item \code{channel},
#' \item \code{room},
#' \item \code{tunnel},
#' \item \code{underground}.
#' }
#' Type: \code{\link{assert_character}}.
#' }
#'
#' \item{exp5k}{
#' Logical indicator for pipe regime: if \code{TRUE} pipe is
#' operated more that \code{5000} hours per year.
#' Type: \code{\link{assert_logical}}.
#' }
#'
#' \item{insulation}{
#' Identifier of insulation that covers the exterior of pipe:
#' \describe{
#' \item{\code{0}}{no insulation}
#' \item{\code{1}}{foamed polyurethane or analogue}
#' \item{\code{2}}{polymer concrete}
#' }
#' Type: \code{\link{assert_integerish}}.
#' }
#'
#' \item{diameter}{Nominal internal diameter of pipe, [\emph{mm}]. Type: \code{\link{assert_double}}.}
#'
#' \item{temperature}{Operational temperature of pipe, [\emph{°C}]. Type: \code{\link{assert_double}}.}
#'
#' \item{loss}{
#' Normative value of specific heat loss power equal to heat flux output by
#' 1 meter length steel pipe during an hour,
#' [\emph{kcal/m/hour}].
#' Type: \code{\link{assert_double}}.}
#' }
#'
#' @source \url{https://docs.cntd.ru/document/902148459}
"m325nhldata"