When a valve is installed with reducers or other attached fittings, the liquid pressure recovery of the valve-fitting combination is not the same as that for the valve alone. For calculations involving choked flow, it is convenient to treat the piping geometry factor (fp) and the fl factor for the valve-fitting combination as a single factor, flp.
1 |
kv |
Flow coefficient in m3/h |
fl |
Liquid pressure recovery factor of a control valve without attached fittings |
dn |
diameter in millimeter (mm). |
d1 |
Inlet diameter reducer only in millimeter (mm). |
d2 |
Outlet diameter increase only in millimeter (mm). |
Product of the liquid pressure recovery factor of a valve with attached fittings (no symbol has been identified) and the piping geometry factor, dimensionless.