environmental_cof_ehv_switchgear: Environmental cost of Failure for EHV swicthgear & 132kV CB

View source: R/cof_ehv_switchgear.R

environmental_cof_ehv_switchgearR Documentation

Environmental cost of Failure for EHV swicthgear & 132kV CB

Description

This function calculates environmental consequences of failure (cf. section 7.3, page 79, CNAIM, 2021). Environmental consequences of failure is used in the derivation of consequences of failure see cof().#' @return Numeric. Financial consequences of failure for LV switchgear

Usage

environmental_cof_ehv_switchgear(
  ehv_asset_category,
  type_env_factor,
  prox_water,
  bunded
)

Arguments

ehv_asset_category

String The type of EHV swicthgear & 132kV CB Options: ehv_asset_category = c( "33kV CB (Air Insulated Busbars)(ID)(GM)", "33kV CB (Air Insulated Busbars)(OD)(GM)", "33kV CB (Gas Insulated Busbars)(ID)(GM)", "33kV CB (Gas Insulated Busbars)(OD)(GM)", "33kV RMU", "33kV Switch (GM)", "66kV CB (Air Insulated Busbars)(ID)(GM)", "66kV CB (Air Insulated Busbars)(OD)(GM)", "66kV CB (Gas Insulated Busbars)(ID)(GM)", "66kV CB (Gas Insulated Busbars)(OD)(GM)")

type_env_factor

String The type environment factor of EHV asset category

prox_water

Numeric. Specify the proximity to a water course in meters. A setting of "Default" will result in a proximity factor of 1. Thus assume the proximity to a water course is between 80m and 120m (cf. table 231, page 188, CNAIM, 2021).

bunded

String. Options: bunded = c("Yes", "No", "Default"). A setting of "Default" will result in a bunding factor of 1.

Source

DNO Common Network Asset Indices Methodology (CNAIM), Health & Criticality - Version 2.1, 2021: https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf

Examples

environmental_cof_ehv_switchgear(ehv_asset_category = "33kV RMU",
type_env_factor = "Oil",
prox_water = 95,
bunded = "Yes")

CNAIM documentation built on Aug. 31, 2022, 9:13 a.m.