#' @title Financial cost of Failure for EHV swicthgear & 132kV CB
#' @description This function calculates financial consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Financial consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().
#' @param ehv_asset_category String The type of EHV swicthgear & 132kV CB
#' Options: \code{ehv_asset_category = c(
#' "33kV CB (Air Insulated Busbars)(ID)(GM)",
#' "33kV CB (Air Insulated Busbars)(OD)(GM)",
#' "33kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "33kV CB (Gas Insulated Busbars)(OD)(GM)",
#' "33kV RMU",
#' "33kV Switch (GM)",
#' "66kV CB (Air Insulated Busbars)(ID)(GM)",
#' "66kV CB (Air Insulated Busbars)(OD)(GM)",
#' "66kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "66kV CB (Gas Insulated Busbars)(OD)(GM)")}
#' @param access_factor_criteria String. Asses Financial factor criteria for EHV swicthgear & 132kV CB
#' setting (cf. table 221, page 180, CNAIM, 2021).
#' Options: \code{access_factor_criteria = c("Type A", "Type B", "Type C")}.
#' @return Numeric. Financial consequences of failure for EHV swicthgear & 132kV CB
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' financial_cof_ehv_switchgear(ehv_asset_category = "33kV RMU", access_factor_criteria = "Type A")
financial_cof_ehv_switchgear <- function(ehv_asset_category, access_factor_criteria){
`Asset Register Category` = `Health Index Asset Category` = `Asset Category` = NULL
asset_category <- gb_ref$categorisation_of_assets %>%
dplyr::filter(`Asset Register Category` == ehv_asset_category) %>%
dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()
# Reference cost of failure table 16 --------------------------------------
reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
`Asset Register Category` ==
ehv_asset_category)
# Reference financial cost of failure -------------------------------------
fcost <- reference_costs_of_failure_tf$`Financial - (GBP)`
# Type financial factor ---------------------------------------------------
type_financial_factor <- 1
# Access financial factor -------------------------------------------------
access_financial_factor_category <- "EHV Switchgear (GM)"
if("132kV" %in% ehv_asset_category){
access_financial_factor_category <- "132kV CBs"
}
access_financial_factors <- gb_ref$access_factor_swg_tf_asset
access_financial_factors_tf <- dplyr::filter(access_financial_factors,
`Asset Category` ==
access_financial_factor_category)
if (access_factor_criteria == "Type A") {
access_finacial_factor <-
access_financial_factors_tf$
`Access Factor: Type A Criteria - Normal Access ( & Default Value)`
}
else if (access_factor_criteria == "Type B") {
access_finacial_factor <-
access_financial_factors_tf$
`Access Factor: Type B Criteria - Constrained Access or Confined Working Space`
}
else if (access_factor_criteria == "Type C") {
access_finacial_factor <-
access_financial_factors_tf$
`Access Factor: Type C Criteria - Underground substation`
}
# Financial consequences factor -------------------------------------------
fc_factor <- type_financial_factor * access_finacial_factor
# Financial consequences of failure ---------------------------------------
return(fc_factor * fcost)
}
#' @title Safety cost of Failure for EHV swicthgear & 132kV CB
#' @description This function calculates safety consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Safety consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().
#' @param ehv_asset_category String The type of EHV swicthgear & 132kV CB
#' Options: \code{ehv_asset_category = c(
#' "33kV CB (Air Insulated Busbars)(ID)(GM)",
#' "33kV CB (Air Insulated Busbars)(OD)(GM)",
#' "33kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "33kV CB (Gas Insulated Busbars)(OD)(GM)",
#' "33kV RMU",
#' "33kV Switch (GM)",
#' "66kV CB (Air Insulated Busbars)(ID)(GM)",
#' "66kV CB (Air Insulated Busbars)(OD)(GM)",
#' "66kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "66kV CB (Gas Insulated Busbars)(OD)(GM)")}
#' @param location_risk String Type Financial factor criteria for EHV swicthgear & 132kV CB
#' (cf. section D1.2.1, page 178, CNAIM, 2021).
#' Options: \code{location_risk = c("Low", "Medium", "High")}.
#' The default setting is
#' \code{location_risk = "Medium"}.
#' @param type_risk String. Asses Financial factor criteria for EHV swicthgear & 132kV CB
#' setting (cf. table 221, page 180, CNAIM, 2021).
#' Options: \code{type_risk = c("Low", "Medium", "High")}.
#' The default setting is
#' \code{type_risk = "Medium"}.
#' @return Numeric. Financial consequences of failure for EHV swicthgear & 132kV CB
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' safety_cof_ehv_switchgear(ehv_asset_category = "33kV RMU",
#' location_risk = "Default",
#' type_risk = "Default")
safety_cof_ehv_switchgear <- function(ehv_asset_category,
location_risk,
type_risk){
`Asset Register Category` = `Health Index Asset Category` = `Asset Category` = NULL
asset_category <- gb_ref$categorisation_of_assets %>%
dplyr::filter(`Asset Register Category` == ehv_asset_category) %>%
dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()
reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
`Asset Register Category` ==
ehv_asset_category)
# Reference financial cost of failure -------------------------------------
scost <- reference_costs_of_failure_tf$`Safety - (GBP)`
if (location_risk == "Default") location_risk <- "Medium (Default)"
if (location_risk == "Medium") location_risk <- "Medium (Default)"
if (type_risk == "Default") type_risk <- "Medium"
safety_conseq_factor_sg_tf_oh <- gb_ref$safety_conseq_factor_sg_tf_oh
row_no <- which(safety_conseq_factor_sg_tf_oh$
`Safety Consequence Factor - Switchgear, Transformers & Overhead Lines...2` ==
location_risk)
col_no <- grep(type_risk, colnames(safety_conseq_factor_sg_tf_oh))
safety_consequence_factor <- safety_conseq_factor_sg_tf_oh[row_no, col_no]
# Safety consequence of failure -------------------------------------------
safety_cof <- safety_consequence_factor * scost
return(safety_cof)
}
#' @title Environmental cost of Failure for EHV swicthgear & 132kV CB
#' @description This function calculates environmental consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Environmental consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().#' @return Numeric. Financial consequences of failure for LV switchgear
#' @param ehv_asset_category String The type of EHV swicthgear & 132kV CB
#' Options: \code{ehv_asset_category = c(
#' "33kV CB (Air Insulated Busbars)(ID)(GM)",
#' "33kV CB (Air Insulated Busbars)(OD)(GM)",
#' "33kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "33kV CB (Gas Insulated Busbars)(OD)(GM)",
#' "33kV RMU",
#' "33kV Switch (GM)",
#' "66kV CB (Air Insulated Busbars)(ID)(GM)",
#' "66kV CB (Air Insulated Busbars)(OD)(GM)",
#' "66kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "66kV CB (Gas Insulated Busbars)(OD)(GM)")}
#' @param type_env_factor String The type environment factor of EHV asset category
#' @param prox_water Numeric. Specify the proximity to a water course in meters.
#' A setting of \code{"Default"} will result in a proximity factor of 1. Thus
#' assume the proximity to a water course is between 80m and 120m
#' (cf. table 231, page 188, CNAIM, 2021).
#' @param bunded String. Options: \code{bunded = c("Yes", "No", "Default")}.
#' A setting of \code{"Default"} will result in a bunding factor of 1.
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' environmental_cof_ehv_switchgear(ehv_asset_category = "33kV RMU",
#' type_env_factor = "Oil",
#' prox_water = 95,
#' bunded = "Yes")
environmental_cof_ehv_switchgear <- function(ehv_asset_category,
type_env_factor,
prox_water,
bunded){
`Asset Register Category` = `Health Index Asset Category` = `Asset Category` =
`Type environment factor` = NULL
asset_category <- gb_ref$categorisation_of_assets %>%
dplyr::filter(`Asset Register Category` == ehv_asset_category) %>%
dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()
reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
`Asset Register Category` ==
ehv_asset_category)
# Reference financial cost of failure -------------------------------------
ecost <- reference_costs_of_failure_tf$`Environmental - (GBP)`
# Type env factor -------------------------------------
asset_type_env_factor <- gb_ref$type_enviromental_factor %>%
dplyr::filter(`Type environment factor` == asset_category)
type_environmental_factor <- asset_type_env_factor[[type_env_factor]]
# Size env factor -------------------------------------
size_environmental_factor <- 1
# Location environmetal factor table 231 ----------------------------------
location_environ_al_factor <- gb_ref$location_environ_al_factor
location_environ_al_factor_tf <- dplyr::filter(location_environ_al_factor,
`Asset Register Category` ==
asset_category)
# Bunded "Yes", "No", "Default" ?
if (bunded == "Default") {
bunding_factor <- 1
} else if (bunded == "Yes") {
bunding_factor <-
location_environ_al_factor_tf$`Bunding Factor: Bunded`
} else if (bunded == "No") {
bunding_factor <-
location_environ_al_factor_tf$`Bunding Factor: Not bunded`
}
# Proximity to water.
if(prox_water == "Default") {
prox_factor <- 1
} else if (prox_water >= 40 && prox_water < 80) {
prox_factor <- location_environ_al_factor_tf$
`Proximity Factor: Close to Water Course (between 40m and 80m)`
} else if (prox_water >= 80 && prox_water < 120) {
prox_factor <- location_environ_al_factor_tf$
`Proximity Factor: Moderately Close to Water Course (between 80m and 120m)`
} else if (prox_water > 120) {
prox_factor <- location_environ_al_factor_tf$
`Proximity Factor: Not Close to Water Course (>120m) or No Oil`
} else if (prox_water < 40) {
prox_factor <- location_environ_al_factor_tf$
`Proximity Factor: Very Close to Water Course (<40m)`
}
# Location environmental factor
location_environmental_factor <- prox_factor * bunding_factor
environmental_consequences_factor <- (type_environmental_factor *
size_environmental_factor *
location_environmental_factor)
# Environmental consequences ----------------------------------------------
environmental_cof <- environmental_consequences_factor * ecost
return(environmental_cof)
}
#' @title Network cost of Failure for EHV swicthgear & 132kV CB
#' @description This function calculates network cost of failure for
#' all asset categories exclusive the assets EHV and 132kV transformers.
#' (cf. section 7.6, page 87, CNAIM, 2021). Network cost of failure
#' is used in the derivation of consequences of failure see \code{\link{cof}}().
#' @param ehv_asset_category String The type of EHV swicthgear & 132kV CB
#' Options: \code{ehv_asset_category = c(
#' "33kV CB (Air Insulated Busbars)(ID)(GM)",
#' "33kV CB (Air Insulated Busbars)(OD)(GM)",
#' "33kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "33kV CB (Gas Insulated Busbars)(OD)(GM)",
#' "33kV RMU",
#' "33kV Switch (GM)",
#' "66kV CB (Air Insulated Busbars)(ID)(GM)",
#' "66kV CB (Air Insulated Busbars)(OD)(GM)",
#' "66kV CB (Gas Insulated Busbars)(ID)(GM)",
#' "66kV CB (Gas Insulated Busbars)(OD)(GM)")}
#' @param actual_load_mva Numeric. The actual load on the asset
#' @param secure Boolean If the asset is in a secure network or not
#' @return Numeric. Network cost of failure.
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' network_cof_ehv_switchgear(ehv_asset_category = "33kV RMU",
#' actual_load_mva = 15)
network_cof_ehv_switchgear<- function(ehv_asset_category,
actual_load_mva,
secure = T) {
`Asset Register Category` = `Health Index Asset Category` = `Asset Category` =
`Maximum Demand Used To Derive Reference Cost (MVA)` = NULL
reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
`Asset Register Category` ==
ehv_asset_category)
# Reference financial cost of failure -------------------------------------
ncost <- reference_costs_of_failure_tf$`Network Performance - (GBP)`
# Load factor ---------------------------------------------------------
ref_nw_perf_cost_fail_ehv_df <- gb_ref$ref_nw_perf_cost_of_fail_ehv
ref_nw_perf_cost_fail_ehv_single_row_df <- dplyr::filter(ref_nw_perf_cost_fail_ehv_df,
`Asset Category` ==
ehv_asset_category)
load_factor <- actual_load_mva/ref_nw_perf_cost_fail_ehv_single_row_df$`Maximum Demand Used To Derive Reference Cost (MVA)`
# Network type factor -----------------------------------
network_type_factor <- 1
if(!secure){
network_type_factor <- 2.5
}
# Network perfomance consequence factor -----------------------------------
network_performance_consequence_factor <- load_factor *
network_type_factor
# Network performance cost of failure -------------------------------------
network_cof <- network_performance_consequence_factor * ncost
return(network_cof)
}
Any scripts or data that you put into this service are public.