This function calculates the current annual probability of failure per kilometer 132kV Switchgear The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function. For more information about the probability of failure function see section 6 on page 34 in CNAIM (2021).
pof_132kv_cb( cb_asset_category = "132kV CB (Air Insulated Busbars)(ID) (GM)", placement = "Default", number_of_operations = "Default", altitude_m = "Default", distance_from_coast_km = "Default", corrosion_category_index = "Default", age, measured_condition_inputs, observed_condition_inputs, reliability_factor = "Default" )
| cb_asset_category | String The type of 132kV asset category | 
| placement | String. Specify if the asset is located outdoor or indoor. | 
| number_of_operations | The number of operations for duty factor | 
| altitude_m | Numeric. Specify the altitude location for
the asset measured in meters from sea level. | 
| distance_from_coast_km | Numeric. Specify the distance from the
coast measured in kilometers.  | 
| corrosion_category_index | Integer. Specify the corrosion index category, 1-5. | 
| age | Numeric. The current age in years of the conductor. | 
| measured_condition_inputs | Named list observed_conditions_input | 
| observed_condition_inputs | Named list observed_conditions_input
 | 
| reliability_factor | Numeric.  | 
DataFrame Current probability of failure per annum per kilometer along with current health score.
DNO Common Network Asset Indices Methodology (CNAIM), Health & Criticality - Version 2.1, 2021: https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf
# Current annual probability of failure for EHV Swicthgear
pof_132kv_cb(
cb_asset_category = "132kV CB (Air Insulated Busbars)(ID) (GM)",
number_of_operations = "Default",
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_condition" =
list("Condition Criteria: Observed Condition" = "Default"),
"oil_gas" = list("Condition Criteria: Observed Condition" = "Default"),
"thermo_assment" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_condition" = list("Condition Criteria: Observed Condition" = "Default"),
"indoor_env" = list("Condition Criteria: Observed Condition" = "Default"),
"support_structure" = list("Condition Criteria: Observed Condition" = "Default"),
"air_systems" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("partial_discharge" =
list("Condition Criteria: Partial Discharge Test Results" = "Default"),
"ductor_test" = list("Condition Criteria: Ductor Test Results" = "Default"),
"oil_test" = list("Condition Criteria: Oil Test/ Gas Test Results" = "Default"),
"temp_reading" = list("Condition Criteria: Temperature Readings" = "Default"),
"trip_test" = list("Condition Criteria: Trip Timing Test Result" = "Default"),
"ir_test" = list("Condition Criteria: IR Test Results" = "Default" )),
reliability_factor = "Default")