View source: R/pof_board_04kv.R
| pof_board_04kv | R Documentation |
This function calculates the current annual probability of failure for 0.4kV Board The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function. A sting that refers to the specific asset category.
pof_board_04kv( placement = "Default", altitude_m = "Default", distance_from_coast_km = "Default", corrosion_category_index = "Default", age, measured_condition_inputs, observed_condition_inputs, reliability_factor = "Default", k_value = 0.0069, c_value = 1.087, normal_expected_life = 60 )
placement |
String. Specify if the asset is located outdoor or indoor. |
altitude_m |
Numeric. Specify the altitude location for
the asset measured in meters from sea level. |
distance_from_coast_km |
Numeric. Specify the distance from the
coast measured in kilometers. |
corrosion_category_index |
Integer. Specify the corrosion index category, 1-5. |
age |
Numeric. The current age in years of the conductor. |
measured_condition_inputs |
Named list observed_conditions_input |
observed_condition_inputs |
Named list observed_conditions_input
|
reliability_factor |
Numeric. |
k_value |
Numeric. |
c_value |
Numeric. |
normal_expected_life |
Numeric. |
DataFrame Current probability of failure per annum per kilometer along with current health score.
# Current annual probability of failure for 0.4kV board
pof_board_04kv(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_cond" =
list("Condition Criteria: Observed Condition" = "Default"),
"compound_leaks" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_cond" = list("Condition Criteria: Observed Condition" = "Default"),
"insulation" = list("Condition Criteria: Observed Condition" = "Default"),
"signs_heating" = list("Condition Criteria: Observed Condition" = "Default"),
"phase_barriers" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("opsal_adequacy" =
list("Condition Criteria: Operational Adequacy" = "Default")),
reliability_factor = "Default",
k_value = 0.0069,
c_value = 1.087,
normal_expected_life = 60)
Add the following code to your website.
For more information on customizing the embed code, read Embedding Snippets.