pof_future_board_04kv: Future Probability of Failure for 0.4kV Board

View source: R/pof_future_board_04kv.R

pof_future_board_04kvR Documentation

Future Probability of Failure for 0.4kV Board

Description

This function calculates the future annual probability of failure per kilometer 0.4kV board. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.

Usage

pof_future_board_04kv(
  placement = "Default",
  altitude_m = "Default",
  distance_from_coast_km = "Default",
  corrosion_category_index = "Default",
  age,
  measured_condition_inputs,
  observed_condition_inputs,
  reliability_factor = "Default",
  k_value = 0.0069,
  c_value = 1.087,
  normal_expected_life = 60,
  simulation_end_year = 100
)

Arguments

placement

String. Specify if the asset is located outdoor or indoor.

altitude_m

Numeric. Specify the altitude location for the asset measured in meters from sea level.altitude_m is used to derive the altitude factor. A setting of "Default" will set the altitude factor to 1 independent of asset_type.

distance_from_coast_km

Numeric. Specify the distance from the coast measured in kilometers. distance_from_coast_km is used to derive the distance from coast factor. A setting of "Default" will set the distance from coast factor to 1 independent of asset_type.

corrosion_category_index

Integer. Specify the corrosion index category, 1-5.

age

Numeric. The current age in years of the conductor.

measured_condition_inputs

Named list observed_conditions_input

observed_condition_inputs

Named list observed_conditions_input conductor_samp = c("Low","Medium/Normal","High","Default").

reliability_factor

Numeric. reliability_factor shall have a value between 0.6 and 1.5. A setting of "Default" sets the reliability_factor to 1. See section 6.14 on page 73 in CNAIM (2021).

k_value

Numeric. k_value = 0.0069 by default. This number is given in a percentage. The default value is accordingly to the CNAIM standard on p. 110.

c_value

Numeric. c_value = 1.087 by default. The default value is accordingly to the CNAIM standard see page 110

normal_expected_life

Numeric. normal_expected_life = 60 by default. The default value is accordingly to the CNAIM standard on page 107.

simulation_end_year

Numeric. The last year of simulating probability of failure. Default is 100.

Value

DataFrame. Future probability of failure along with future health score

Examples

# Future annual probability of failure for 0.4kV board
pof_future_board_04kv(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_cond" =
list("Condition Criteria: Observed Condition" = "Default"),
"compound_leaks" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_cond" = list("Condition Criteria: Observed Condition" = "Default"),
"insulation" = list("Condition Criteria: Observed Condition" = "Default"),
"signs_heating" = list("Condition Criteria: Observed Condition" = "Default"),
"phase_barriers" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("opsal_adequacy" =
list("Condition Criteria: Operational Adequacy" = "Default")),
reliability_factor = "Default",
k_value = 0.0069,
c_value = 1.087,
normal_expected_life = 60,
simulation_end_year = 100)