View source: R/pof_future_ohl_cond_132_66_33kv.R
pof_future_ohl_cond_132_66_33kv | R Documentation |
This function calculates the future annual probability of failure per kilometer 33-132kV OHL conductors. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function. For more information about the probability of failure function see section 6 on page 34 in CNAIM (2021).
pof_future_ohl_cond_132_66_33kv( ohl_conductor = "66kV OHL (Tower Line) Conductor", sub_division = "Cu", placement = "Default", altitude_m = "Default", distance_from_coast_km = "Default", corrosion_category_index = "Default", age, conductor_samp = "Default", corr_mon_survey = "Default", visual_cond = "Default", midspan_joints = "Default", reliability_factor = "Default", simulation_end_year = 100 )
ohl_conductor |
String.
A sting that refers to the specific asset category.
See See page 17, table 1 in CNAIM (2021).
Options:
|
sub_division |
String. Refers to material the conductor is
made of. Options:
|
placement |
String. Specify if the asset is located outdoor or indoor.
A setting of |
altitude_m |
Numeric. Specify the altitude location for
the asset measured in meters from sea level. |
distance_from_coast_km |
Numeric. Specify the distance from the
coast measured in kilometers. |
corrosion_category_index |
Integer.
Specify the corrosion index category, 1-5.
|
age |
Numeric. The current age in years of the conductor. |
conductor_samp |
String. Conductor sampling. Options:
|
corr_mon_survey |
String. Corrosion monitoring survey. Options:
|
visual_cond |
String. Visual condition. Options:
|
midspan_joints |
Integer. Number of midspan joints on the conductor. A span includes all conductors in that span. See page 146, table 141 and 143 in CNAIM (2021). |
reliability_factor |
Numeric. |
simulation_end_year |
Numeric. The last year of simulating probability of failure. Default is 100. |
DataFrame. Future probability of failure along with future health score
DNO Common Network Asset Indices Methodology (CNAIM), Health & Criticality - Version 2.1, 2021: https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf
# Future annual probability of failure for 66kV OHL (Tower Line) Conductor pof_future_ohl_cond_132_66_33kv( ohl_conductor = "66kV OHL (Tower Line) Conductor", sub_division = "Cu", placement = "Default", altitude_m = "Default", distance_from_coast_km = "Default", corrosion_category_index = "Default", age = 10, conductor_samp = "Default", corr_mon_survey = "Default", visual_cond = "Default", midspan_joints = "Default", reliability_factor = "Default", simulation_end_year = 100)
Add the following code to your website.