View source: R/pof_future_pillar_04kv.R
| pof_future_pillar_04kv | R Documentation | 
This function calculates the future annual probability of failure per kilometer 0.4kV Pillar. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.
pof_future_pillar_04kv( placement = "Default", altitude_m = "Default", distance_from_coast_km = "Default", corrosion_category_index = "Default", age, measured_condition_inputs, observed_condition_inputs, reliability_factor = "Default", k_value = 0.0046, c_value = 1.087, normal_expected_life = 60, simulation_end_year = 100 )
| placement | String. Specify if the asset is located outdoor or indoor. | 
| altitude_m | Numeric. Specify the altitude location for
the asset measured in meters from sea level. | 
| distance_from_coast_km | Numeric. Specify the distance from the
coast measured in kilometers.  | 
| corrosion_category_index | Integer. Specify the corrosion index category, 1-5. | 
| age | Numeric. The current age in years of the conductor. | 
| measured_condition_inputs | Named list observed_conditions_input | 
| observed_condition_inputs | Named list observed_conditions_input
 | 
| reliability_factor | Numeric.  | 
| k_value | Numeric.  | 
| c_value | Numeric.  | 
| normal_expected_life | Numeric.  | 
| simulation_end_year | Numeric. The last year of simulating probability of failure. Default is 100. | 
DataFrame. Future probability of failure along with future health score
# Future annual probability of failure for 0.4kV Pillar
pof_future_pillar_04kv(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_cond" =
list("Condition Criteria: Observed Condition" = "Default"),
"compound_leaks" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_cond" = list("Condition Criteria: Observed Condition" = "Default"),
"insulation" = list("Condition Criteria: Observed Condition" = "Default"),
"signs_heating" = list("Condition Criteria: Observed Condition" = "Default"),
"phase_barriers" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("opsal_adequacy" =
list("Condition Criteria: Operational Adequacy" = "Default")),
reliability_factor = "Default",
k_value = 0.0046,
c_value = 1.087,
normal_expected_life = 60,
simulation_end_year = 100)
Add the following code to your website.