pof_future_rtu: Future Probability of Failure for RTU

View source: R/pof_future_rtu.R

pof_future_rtuR Documentation

Future Probability of Failure for RTU

Description

This function calculates the future annual probability of failure RTU. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.

Usage

pof_future_rtu(
  placement = "Default",
  altitude_m = "Default",
  distance_from_coast_km = "Default",
  corrosion_category_index = "Default",
  age,
  measured_condition_inputs,
  observed_condition_inputs,
  reliability_factor = "Default",
  k_value = 0.128,
  c_value = 1.087,
  normal_expected_life = 20,
  simulation_end_year = 100
)

Arguments

placement

String. Specify if the asset is located outdoor or indoor.

altitude_m

Numeric. Specify the altitude location for the asset measured in meters from sea level.altitude_m is used to derive the altitude factor. See page 111, table 23 in CNAIM (2021). A setting of "Default" will set the altitude factor to 1 independent of asset_type.

distance_from_coast_km

Numeric. Specify the distance from the coast measured in kilometers. distance_from_coast_km is used to derive the distance from coast factor See page 110, table 22 in CNAIM (2021). A setting of "Default" will set the distance from coast factor to 1 independent of asset_type.

corrosion_category_index

Integer. Specify the corrosion index category, 1-5.

age

Numeric. The current age in years of the conductor.

measured_condition_inputs

Named list observed_conditions_input

observed_condition_inputs

Named list observed_conditions_input conductor_samp = c("Low","Medium/Normal","High","Default"). See page 161, table 199 and 201 in CNAIM (2021).

reliability_factor

Numeric. reliability_factor shall have a value between 0.6 and 1.5. A setting of "Default" sets the reliability_factor to 1. See section 6.14 on page 73 in CNAIM (2021).

k_value

Numeric. k_value = 0.0069 by default. This number is given in a percentage. The default value is accordingly to the CNAIM standard on p. 110.

c_value

Numeric. c_value = 1.087 by default. The default value is accordingly to the CNAIM standard see page 110

normal_expected_life

Numeric. normal_expected_life = 60 by default. The default value is accordingly to the CNAIM standard on page 107.

simulation_end_year

Numeric. The last year of simulating probability of failure. Default is 100.

Value

DataFrame. Future probability of failure along with future health score

Examples

 # future annual probability of failure for RTU
pof_future_rtu(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 1,
observed_condition_inputs =
list("external_condition" =
list("Condition Criteria: Observed Condition" = "Default"),
"oil_gas" = list("Condition Criteria: Observed Condition" = "Default"),
"thermo_assment" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_condition" = list("Condition Criteria: Observed Condition" = "Default"),
"indoor_env" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("partial_discharge" =
list("Condition Criteria: Partial Discharge Test Results" = "Default"),
"ductor_test" = list("Condition Criteria: Ductor Test Results" = "Default"),
"oil_test" = list("Condition Criteria: Oil Test Results" = "Default"),
"temp_reading" = list("Condition Criteria: Temperature Readings" = "Default"),
"trip_test" = list("Condition Criteria: Trip Timing Test Result" = "Default")),
reliability_factor = "Default",
k_value = 0.128,
c_value = 1.087,
normal_expected_life = 20,
simulation_end_year = 100)

CNAIM documentation built on Aug. 31, 2022, 9:13 a.m.