pof_future_submarine_cables_30_60kv_oil: Future Probability of Failure for 30kV and 60kV Oil Submarine...

View source: R/pof_future_submarine_cables_30_60kv_oil.R

pof_future_submarine_cables_30_60kv_oilR Documentation

Future Probability of Failure for 30kV and 60kV Oil Submarine Cables

Description

This function calculates the future annual probability of failure per kilometer for a 30kV and 60kV oil submarine cables The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.

Usage

pof_future_submarine_cables_30_60kv_oil(
  utilisation_pct = "Default",
  operating_voltage_pct = "Default",
  topography = "Default",
  sitution = "Default",
  wind_wave = "Default",
  intensity = "Default",
  landlocked = "no",
  sheath_test = "Default",
  partial_discharge = "Default",
  fault_hist = "Default",
  condition_armour = "Default",
  age,
  reliability_factor = "Default",
  k_value = 2.0944,
  c_value = 1.087,
  normal_expected_life = 60,
  simulation_end_year = 100
)

Arguments

utilisation_pct

Numeric. The max percentage of utilisation under normal operating conditions.

operating_voltage_pct

Numeric. The ratio in percent of operating/design voltage.

topography

String Topography

sitution

String Situation

wind_wave

String Wind Wave

intensity

String Intensity

landlocked

String Land Locked

sheath_test

String. Only applied for non pressurised cables. Indicating the state of the sheath. Options: sheath_test = c("Pass", "Failed Minor", "Failed Major", "Default").

partial_discharge

String. Only applied for non pressurised cables. Indicating the level of partial discharge. Options: partial_discharge = c("Low", "Medium", "High", "Default").

fault_hist

Numeric. Only applied for non pressurised cables. The calculated fault rate for the cable in the period per kilometer. A setting of "No historic faults recorded" indicates no fault.

condition_armour

String Condition Armour

age

Numeric. The current age in years of the cable.

reliability_factor

Numeric. reliability_factor shall have a value between 0.6 and 1.5. A setting of "Default" sets the reliability_factor to 1. See section 6.14 on page 73 in CNAIM (2021).

k_value

Numeric. k_value = 0.0658 by default.

c_value

Numeric. c_value = 1.087 by default. The default value is accordingly to the CNAIM standard see page 110

normal_expected_life

Numeric. normal_expected_life = 80 by default.

simulation_end_year

Numeric. The last year of simulating probability of failure. Default is 100.

Value

DataFrame. Future probability of failure along with future health score

Examples

pof_future_submarine_cables_30_60kv_oil(
utilisation_pct = "Default",
operating_voltage_pct = "Default",
topography = "Default",
sitution = "Default",
wind_wave = "Default",
intensity = "Default",
landlocked = "no",
sheath_test = "Default",
partial_discharge = "Default",
fault_hist = "Default",
condition_armour = "Default",
age = 10,
reliability_factor = "Default",
k_value = 0.0202,
c_value = 1.087,
normal_expected_life = 60,
simulation_end_year = 100)