pof_future_switchgear_30_60kv: Future Probability of Failure for 30kV and 60kV Switchgear

View source: R/pof_future_switchgear_30_60kv.R

pof_future_switchgear_30_60kvR Documentation

Future Probability of Failure for 30kV and 60kV Switchgear

Description

This function calculates the future annual probability of failure 30kV and 60kV switchgear. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.

Usage

pof_future_switchgear_30_60kv(
  asset_type = "30kV",
  placement = "Default",
  number_of_operations = "Default",
  altitude_m = "Default",
  distance_from_coast_km = "Default",
  corrosion_category_index = "Default",
  age,
  measured_condition_inputs,
  observed_condition_inputs,
  reliability_factor = "Default",
  k_value = "Default",
  c_value = 1.087,
  normal_expected_life = 55,
  simulation_end_year = 100
)

Arguments

asset_type

String Asset Type

placement

String Placement

number_of_operations

String Number of Operations

altitude_m

String Altitude

distance_from_coast_km

String Distance from coast

corrosion_category_index

String Corrosion Category Index

age

Numeric Age

measured_condition_inputs

Named list observed_conditions_input

observed_condition_inputs

Named list observed_conditions_input

reliability_factor

String Reliability Factor

k_value

Numeric. k_value = 0.0077 by default. This number is given in a percentage. The default value is accordingly to the standard "DE-10kV apb kabler CNAIM" on p. 34.

c_value

Numeric. c_value = 1.087 by default. The default value is accordingly to the CNAIM standard see page 110

normal_expected_life

Numeric. normal_expected_life = 55 by default. The default value is accordingly to the standard "DE-10kV apb kabler CNAIM" on p. 33.

simulation_end_year

Numeric. The last year of simulating probability of failure. Default is 100.

Value

Numeric. Current probability of failure per annum.

Examples

# Future annual probability of failure for 30kV and 60kV Swicthgear
pof_future_switchgear_30_60kv(
asset_type = "30kV",
number_of_operations = "Default",
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_condition" =
list("Condition Criteria: Observed Condition" = "Default"),
"oil_gas" = list("Condition Criteria: Observed Condition" = "Default"),
"thermo_assment" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_condition" = list("Condition Criteria: Observed Condition" = "Default"),
"indoor_env" = list("Condition Criteria: Observed Condition" = "Default"),
"support_structure" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("partial_discharge" =
list("Condition Criteria: Partial Discharge Test Results" = "Default"),
"ductor_test" = list("Condition Criteria: Ductor Test Results" = "Default"),
"oil_test" = list("Condition Criteria: Oil Test Results" = "Default"),
"temp_reading" = list("Condition Criteria: Temperature Readings" = "Default"),
"trip_test" = list("Condition Criteria: Trip Timing Test Result" = "Default"),
"ir_test" = list("Condition Criteria: IR Test Results" = "Default" )),
reliability_factor = "Default",
k_value = "Default",
c_value = 1.087,
normal_expected_life = 55,
simulation_end_year = 100)

CNAIM documentation built on Aug. 31, 2022, 9:13 a.m.