CalcPsychrometricsFromTWetBulb: Calculate psychrometric values from wet-bulb temperature.

Description Usage Arguments Value Examples

Description

Utility function to calculate humidity ratio, dew-point temperature, relative humidity, vapour pressure, moist air enthalpy, moist air volume, and degree of saturation of air given dry-bulb temperature, wet-bulb temperature, and pressure.

Usage

1
CalcPsychrometricsFromTWetBulb(TDryBulb, TWetBulb, Pressure)

Arguments

TDryBulb

A numeric vector of dry-bulb temperature in degreeF [IP] or degreeC [SI]

TWetBulb

A numeric vector of wet-bulb temperature in degreeF [IP] or degreeC [SI]

Pressure

A numeric vector of atmospheric pressure in Psi [IP] or Pa [SI]

Value

A list with named components for each psychrometric value computed:

HumRatio

Humidity ratio in lb_H2O lb_Air-1 [IP] or kg_H2O kg_Air-1 [SI]

TDewPoint

Dew-point temperature in degreeF [IP] or degreeC [SI]

RelHum

Relative humidity in range [0, 1]

VapPres

Partial pressure of water vapor in moist air in Psi [IP] or Pa [SI]

MoistAirEnthalpy

Moist air enthalpy in Btu lb-1 [IP] or J kg-1 [SI]

MoistAirVolume

Specific volume of moist air in ft3 lb-1 [IP] or in m3 kg-1 [SI]

DegreeOfSaturation

Degree of saturation [unitless]

Examples

1
2
3
4
5
SetUnitSystem("IP")
CalcPsychrometricsFromTWetBulb(80:100, 65.0, 14.696)

SetUnitSystem("SI")
CalcPsychrometricsFromTWetBulb(25:40, 20, 101325.0)