GetSatVapPres: Return saturation vapor pressure given dry-bulb temperature.

Description Usage Arguments Value Note References Examples

Description

Return saturation vapor pressure given dry-bulb temperature.

Usage

1
GetSatVapPres(TDryBulb)

Arguments

TDryBulb

A numeric vector of dry-bulb temperature in degreeF [IP] or degreeC [SI]

Value

A numeric vector of vapor pressure of saturated air in Psi [IP] or Pa [SI]

Note

Important note: the ASHRAE formulae are defined above and below the freezing point but have a discontinuity at the freezing point. This is a small inaccuracy on ASHRAE's part: the formulae should be defined above and below the triple point of water (not the feezing point) in which case the discontinuity vanishes. It is essential to use the triple point of water otherwise function GetTDewPointFromVapPres, which inverts the present function, does not converge properly around the freezing point.

References

ASHRAE Handbook - Fundamentals (2017) ch. 1 eqn 5 & 6