R/cof_hv_switchgear_primary.R

Defines functions network_cof_hv_switchgear_primary environmental_cof_hv_switchgear_primary safety_cof_hv_switchgear_primary financial_cof_hv_switchgear_primary

Documented in environmental_cof_hv_switchgear_primary financial_cof_hv_switchgear_primary network_cof_hv_switchgear_primary safety_cof_hv_switchgear_primary

#' @title Financial cost of Failure for HV swicthgear primary
#' @description This function calculates financial consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Financial consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().
#' @param hv_asset_category String The type of HV switchgear distribution asset category
#' Options: \code{hv_asset_category = c("6.6/11kV CB (GM) Primary",
#' "20kV CB (GM) Primary")}
#' @param access_factor_criteria String. Asses Financial factor criteria for HV switchgear
#' setting (cf. table 221, page 180, CNAIM, 2021).
#' Options: \code{access_factor_criteria = c("Type A", "Type B", "Type C")}.
#' @return Numeric. Financial consequences of failure for HV switchgear primary
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' financial_cof_hv_switchgear_primary(
#' hv_asset_category = "6.6/11kV CB (GM) Primary",
#' access_factor_criteria = "Type A")
financial_cof_hv_switchgear_primary <- function(hv_asset_category,
                                                access_factor_criteria){
  `Asset Register Category` = `Health Index Asset Category` = `Asset Category` = NULL

  asset_category <- gb_ref$categorisation_of_assets %>%
    dplyr::filter(`Asset Register Category` == hv_asset_category) %>%
    dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()

  # Reference cost of failure table 16 --------------------------------------
  reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
                                                 `Asset Register Category` ==
                                                   hv_asset_category)

  # Reference financial cost of failure -------------------------------------
  fcost <- reference_costs_of_failure_tf$`Financial - (GBP)`

  # Type financial factor ---------------------------------------------------
  type_financial_factor <- 1

  # Access financial factor -------------------------------------------------
  access_financial_factors <- gb_ref$access_factor_swg_tf_asset
  access_financial_factors_tf <- dplyr::filter(access_financial_factors,
                                               `Asset Category` ==
                                                 "HV Switchgear (GM) - Distribution")

  if (access_factor_criteria == "Type A") {
    access_finacial_factor <-
      access_financial_factors_tf$
      `Access Factor: Type A Criteria - Normal Access ( & Default Value)`
  }
  else if (access_factor_criteria == "Type B") {
    access_finacial_factor <-
      access_financial_factors_tf$
      `Access Factor: Type B Criteria - Constrained Access or Confined Working Space`
  }
  else if (access_factor_criteria == "Type C") {
    access_finacial_factor <-
      access_financial_factors_tf$
      `Access Factor: Type C Criteria - Underground substation`
  }


  # Financial consequences factor -------------------------------------------
  fc_factor <- type_financial_factor * access_finacial_factor

  # Financial consequences of failure ---------------------------------------
  return(fc_factor * fcost)
}


#' @title Safety cost of Failure for HV Switchgear Primary
#' @description This function calculates safety consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Safetyr consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().
#' @param hv_asset_category String The type of HV asset category
#' Options: \code{hv_asset_category = c("6.6/11kV CB (GM) Primary",
#' "20kV CB (GM) Primary")}
#' @param location_risk String Type Financial factor criteria for HV switchgear
#' (cf. section D1.2.1, page 178, CNAIM, 2021).
#' Options: \code{location_risk = c("Low", "Medium", "High")}.
#' The default setting is
#' \code{location_risk = "Medium"}.
#' @param type_risk String. Asses Financial factor criteria for HV switchgear
#' setting (cf. table 218, page 176, CNAIM, 2021).
#' Options: \code{type_risk = c("Low", "Medium", "High")}.
#' The default setting is
#' \code{type_risk = "Medium"}.
#' @return Numeric. Financial consequences of failure for HV switchgear
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' safety_cof_hv_switchgear_primary(
#' hv_asset_category = "6.6/11kV CB (GM) Primary",
#' location_risk = "Default",
#' type_risk = "Default")
safety_cof_hv_switchgear_primary <- function(hv_asset_category,
                                             location_risk,
                                             type_risk){
  `Asset Register Category` = `Health Index Asset Category` = `Asset Category` = NULL

  asset_category <- gb_ref$categorisation_of_assets %>%
    dplyr::filter(`Asset Register Category` == hv_asset_category) %>%
    dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()

  reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
                                                 `Asset Register Category` ==
                                                   hv_asset_category)

  # Reference financial cost of failure -------------------------------------
  scost <- reference_costs_of_failure_tf$`Safety - (GBP)`

  if (location_risk == "Default") location_risk <- "Medium (Default)"
  if (location_risk == "Medium") location_risk <- "Medium (Default)"
  if (type_risk == "Default") type_risk <- "Medium"

  safety_conseq_factor_sg_tf_oh <- gb_ref$safety_conseq_factor_sg_tf_oh

  row_no <- which(safety_conseq_factor_sg_tf_oh$
                    `Safety Consequence Factor - Switchgear, Transformers & Overhead Lines...2` ==
                    location_risk)

  col_no <- grep(type_risk, colnames(safety_conseq_factor_sg_tf_oh))

  safety_consequence_factor <- safety_conseq_factor_sg_tf_oh[row_no, col_no]

  # Safety consequence of failure -------------------------------------------
  safety_cof <- safety_consequence_factor * scost

  return(safety_cof)
}


#' @title Environmental cost of Failure for HV switchgear primary
#' @description This function calculates environmental consequences of failure
#' (cf. section 7.3, page 79, CNAIM, 2021). Environmental consequences
#' of failure is used in
#' the derivation of consequences of failure see \code{\link{cof}}().#' @return Numeric. Financial consequences of failure for HV switchgear
#' @param hv_asset_category String The type of HV asset category
#' Options: \code{hv_asset_category = c("6.6/11kV CB (GM) Primary",
#' "20kV CB (GM) Primary")}
#' @param type_env_factor String The type environment factor of HV asset category
#' Options: \code{type_env_factor = c("Oil", "SF6", "Niether", "Default")}.
#' @param prox_water Numeric. Specify the proximity to a water course in meters.
#' A setting of \code{"Default"} will result in a proximity factor of 1. Thus
#' assume the proximity to a water course is between 80m and 120m
#' (cf. table 231, page 188, CNAIM, 2021).
#' @param bunded String. Options: \code{bunded = c("Yes", "No", "Default")}.
#' A setting of \code{"Default"} will result in a bunding factor of 1.
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' environmental_cof_hv_switchgear_primary(
#' hv_asset_category = "6.6/11kV CB (GM) Primary",
#' type_env_factor = "Oil",
#' prox_water = 95, bunded = "Yes")
environmental_cof_hv_switchgear_primary <- function(hv_asset_category,
                                                    type_env_factor,
                                                    prox_water,
                                                    bunded){
  `Asset Register Category` = `Health Index Asset Category` = `Asset Category` =
    `Type environment factor` = NULL

  asset_category <- gb_ref$categorisation_of_assets %>%
    dplyr::filter(`Asset Register Category` == hv_asset_category) %>%
    dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()

  reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
                                                 `Asset Register Category` ==
                                                   hv_asset_category)

  # Reference financial cost of failure -------------------------------------
  ecost <- reference_costs_of_failure_tf$`Environmental - (GBP)`

  # Type env factor -------------------------------------
  asset_type_env_factor <- gb_ref$type_enviromental_factor %>%
    dplyr::filter(`Type environment factor` == asset_category)

  type_environmental_factor <- asset_type_env_factor[[type_env_factor]]

  # Size env factor -------------------------------------
  size_environmental_factor <- 1

  # Location environmetal factor table 231 ----------------------------------
  location_environ_al_factor <- gb_ref$location_environ_al_factor

  location_environ_al_factor_tf <- dplyr::filter(location_environ_al_factor,
                                                 `Asset Register Category` ==
                                                   asset_category)

  # Bunded "Yes", "No", "Default" ?
  if (bunded == "Default") {
    bunding_factor <- 1
  } else if (bunded == "Yes") {
    bunding_factor <-
      location_environ_al_factor_tf$`Bunding Factor: Bunded`
  } else if (bunded == "No") {
    bunding_factor <-
      location_environ_al_factor_tf$`Bunding Factor: Not bunded`
  }

  # Proximity to water.
  if(prox_water == "Default") {
    prox_factor <- 1
  } else if (prox_water >= 40 && prox_water < 80) {
    prox_factor <- location_environ_al_factor_tf$
      `Proximity Factor: Close to Water Course (between 40m and 80m)`
  } else if (prox_water >= 80 && prox_water < 120) {
    prox_factor <- location_environ_al_factor_tf$
      `Proximity Factor: Moderately Close to Water Course (between 80m and 120m)`
  } else if (prox_water > 120) {
    prox_factor <- location_environ_al_factor_tf$
      `Proximity Factor: Not Close to Water Course (>120m) or No Oil`
  } else if (prox_water < 40) {
    prox_factor <- location_environ_al_factor_tf$
      `Proximity Factor: Very Close to Water Course (<40m)`
  }

  # Location environmental factor
  location_environmental_factor <- prox_factor * bunding_factor

  environmental_consequences_factor <- (type_environmental_factor *
                                          size_environmental_factor *
                                          location_environmental_factor)

  # Environmental consequences ----------------------------------------------
  environmental_cof <- environmental_consequences_factor * ecost
  return(environmental_cof)
}


#' @title Network cost of Failure for HV Switchgear Primary
#' @description This function calculates network cost of failure for
#' all asset categories exclusive the assets EHV and 132kV transformers.
#' (cf. section 7.6, page 87, CNAIM, 2021). Network cost of failure
#' is used in the derivation of consequences of failure see \code{\link{cof}}().
#' @param hv_asset_category String The type of HV asset category
#' Options: \code{hv_asset_category = c("6.6/11kV CB (GM) Primary",
#' "20kV CB (GM) Primary")}
#' @param no_customers Numeric. The numner of customers
#' fed by an individual asset.
#' @param kva_per_customer Numeric. If the asset have an exceptionally high
#' demand per customer type in kVA per customer. A setting of \code{"Default"}
#' results in a multiplication factor of 1 (cf. table 18, page 90, CNAIM, 2021).
#' @return Numeric. Network cost of failure.
#' @source DNO Common Network Asset Indices Methodology (CNAIM),
#' Health & Criticality - Version 2.1, 2021:
#' \url{https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf}
#' @export
#' @examples
#' network_cof_hv_switchgear_primary(hv_asset_category = "6.6/11kV CB (GM) Secondary",
#' no_customers = 750, kva_per_customer = 51)
network_cof_hv_switchgear_primary <- function(hv_asset_category,
                                              no_customers,
                                              kva_per_customer = "Default") {

  `Asset Register Category` = `Health Index Asset Category` = `Asset Category` = NULL

  asset_category <- gb_ref$categorisation_of_assets %>%
    dplyr::filter(`Asset Register Category` == hv_asset_category) %>%
    dplyr::select(`Health Index Asset Category`) %>% dplyr::pull()

  reference_costs_of_failure_tf <- dplyr::filter(gb_ref$reference_costs_of_failure,
                                                 `Asset Register Category` ==
                                                   hv_asset_category)

  # Reference financial cost of failure -------------------------------------
  ncost <- reference_costs_of_failure_tf$`Network Performance - (GBP)`

  # Customer factor ---------------------------------------------------------
  ref_nw_perf_cost_fail_lv_hv <- gb_ref$ref_nw_perf_cost_fail_lv_hv
  ref_nw_perf_cost_fail_lv_hv_tf <- dplyr::filter(ref_nw_perf_cost_fail_lv_hv,
                                                  `Asset Category` ==
                                                    asset_category)

  ref_no_cust <-
    ref_nw_perf_cost_fail_lv_hv_tf$`Reference Number of Connected Customers`

  customer_no_adjust_lv_hv_asset <- gb_ref$customer_no_adjust_lv_hv_asset


  for (n in 1:nrow(customer_no_adjust_lv_hv_asset)){
    if (kva_per_customer == 'Default'){
      adj_cust_no <- 1
      break
    } else if (kva_per_customer >= as.numeric(
      customer_no_adjust_lv_hv_asset$Lower[n]) &
      kva_per_customer < as.numeric(
        customer_no_adjust_lv_hv_asset$Upper[n])){
      adj_cust_no <-
        customer_no_adjust_lv_hv_asset$
        `No. of Customers to be used in the derivation of Customer Factor`[n]
      break
    }
  }

  adj_cust_no <- gsub("([0-9]+).*$", "\\1", adj_cust_no) %>% as.numeric()

  customer_factor <- (adj_cust_no * no_customers) / ref_no_cust


  # Customer sensitivity factor ---------------------------------------------
  customer_sensitivity_factor <- 1 # See section 7.6.2.2, p. 89 in CNAIM (2021)


  # Network perfomance consequence factor -----------------------------------

  network_performance_consequence_factor <- customer_factor *
    customer_sensitivity_factor


  # Network performance cost of failure -------------------------------------
  network_cof <- network_performance_consequence_factor * ncost

  return(network_cof)

}